Cable VokselN2XY FIRE RESISTANCE CABLES 4 CORE
Informasi harga, Diskon, Komisi by WA : simpati12 812
1843 3055 (Fast Response)
Types:
N2XY (CU/XLPE/PVC) 1 x 240 mm2 - Str - 0.6/1 (1.2)Kv |
N2XY (CU/XLPE/PVC) 1 x 300 mm2 - Str - 0.6/1 (1.2)Kv |
N2XY (CU/XLPE/PVC) 1 x 120 mm2 - Str - 0.6/1 (1.2)Kv |
N2XY (CU/XLPE/PVC) 1 x 95 mm2 - Str - 0.6/1 (1.2)Kv |
FIRE RESISTANCE CABLES 4 CORE
N2XY 4 x (1.5 - 300) mm² 0.6/1 kV
Cu / MGT / XLPE / LSFH
- (Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
- Standard Specification : SS 299, BS 6387 & IEC 60331
Construction Data Nom
Cross
Section
Area
mm² | Overall
Diameter
approx.
mm | Cable
Weight
approx.
kg/km | 1.5 | 16.5 | 325 | 2.5 | 17.5 | 390 | 4 | 19.0 | 485 | 6 | 20.5 | 605 | 10 | 23.0 | 840 | 16 | 25.5 | 1,125 | 25 | 29.0 | 1,605 | 35 | 32.0 | 2,075 | 50 | 36.0 | 2,630 | 70 | 41.0 | 3,585 | 95 | 44.5 | 4,700 | 120 | 50.0 | 5,850 | 150 | 55.5 | 7,145 | 185 | 61.0 | 8,850 | 240 | 67.5 | 11,315 | 300 | 74.0 | 13,870 |
|
Application :
For wiring of fire resistance safety circuits, such as fire alarm system, emergency lighting and power, public address and emergency voice communication systems in highrise building, control and instrumentation services in industrial, comercial and residential complexes. Special Features on Request : - UV Resistance
- Flame Retardant Cat. A, B, C
- Flame Retardant Non Category
- Heat Resistance
- Anti Termite
- Anti Rodent
- Low Smoke Zero Halagen
Note : Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape. Standard Packing :
1.5 - 70 sqmm supplied in wooden drum @ 1000 meters
95 - 300 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
|
Electrical Data
Conductor |
Inductance
(mH/km) |
Current - Carrying
Capacity at
at 30 °C * |
Short
Circuit curent
at 1 second
Max.
(kA) |
Nom
Cross
Section
Area
mm² |
DC
Resistance
at 20 °C
Max.
(Ω/km) |
AC
Resistance
at 90 °C
Max.
(Ω/km) |
in air
Max.
(A) |
in ground
Max.
(A) |
|
|
|
|
1.5 |
12.1 |
15.429 |
0.315 |
27 |
31 |
0.22 |
2.5 |
7.41 |
9.449 |
0.293 |
35 |
41 |
0.37 |
4 |
4.61 |
5.878 |
0.275 |
47 |
53 |
0.59 |
6 |
3.08 |
3.927 |
0.263 |
59 |
67 |
0.89 |
10 |
1.83 |
2.334 |
0.248 |
81 |
89 |
1.49 |
16 |
1.15 |
1.467 |
0.238 |
108 |
116 |
2.38 |
25 |
0.727 |
0.927 |
0.240 |
146 |
151 |
3.71 |
35 |
0.524 |
0.669 |
0.233 |
180 |
181 |
5.20 |
50 |
0.387 |
0.494 |
0.232 |
212 |
208 |
7.43 |
70 |
0.268 |
0.342 |
0.229 |
265 |
254 |
10.40 |
95 |
0.193 |
0.247 |
0.224 |
327 |
305 |
14.11 |
120 |
0.153 |
0.196 |
0.223 |
379 |
347 |
17.83 |
150 |
0.124 |
0.160 |
0.224 |
442 |
392 |
22.29 |
185 |
0.0991 |
0.128 |
0.225 |
504 |
441 |
27.49 |
240 |
0.0754 |
0.099 |
0.223 |
597 |
511 |
35.66 |
300 |
0.0601 |
0.080 |
0.221 |
685 |
576 |
44.57 |
* Further infromation about rating factor for certain cable arrangement can be found on supplementary technical information